Solar Anti-Backflow Wiring: Connecting an Energy Meter to an Inverter
How does anti-backflow control work?
- The meter's CTs measure power in both directions at the grid connection point.
- The meter reports real-time data to the inverter over a local interface.
- When the total active power is negative, which means reverse current towards the grid, the inverter lowers its output within 2 seconds to match the on-site load, or stores the surplus in the battery first.
- Grid-fed power then stays close to zero while the solar energy is used on site.
Where should the CTs go?
The CTs must see the net flow between the site and the grid. Put them on the live conductors of the main grid feed, upstream of the loads and of the point where the inverter's output joins the installation. A CT placed on the inverter's own output measures solar production, not the grid exchange, and cannot control export.
- Single-phase: one CT on the live conductor.
- Three-phase four-wire: one CT on each of the three phases. The PC4713-W-485 uses three CTs and supports single-phase, split-phase and three-phase four-wire systems; three-phase three-wire and delta systems are not supported.
- Use one live conductor per CT, never the live and neutral together.
- Choose a CT size above the expected peak grid current. The PC4713-W-485 offers 80 A, 120 A (default), 200 A, 300 A, 500 A and 750 A CTs.
How do I wire the meter?
- Switch off the supply and confirm there is no voltage.
- Mount the meter on the DIN rail and connect the power supply and the voltage reference as shown in its quick start guide.
- Clamp the CTs on the grid feed and plug their cables into the meter's CT terminals.
- Follow the CT arrow direction given in the quick start guide of your model. On the single-phase PC4711 the arrow points towards the load.
- Connect the communication path to the inverter (next section).
- Switch the supply on and read the meter.
Which communication method should I choose?
The PC4713-W-485 provides both: Wi-Fi 2.4 GHz (HTTP, MQTT, Modbus TCP) and an RS485 port (Modbus RTU). Its data refresh is 50 ms and the Modbus RTU response time is up to 50 ms. The PC4713-W variant has Wi-Fi only. Protocol documents are available from OWON sales on request.
| Method | Medium | Best for |
|---|---|---|
| Modbus RTU (RS485) | Wired | Stable network, strong anti-interference, low latency, long distance and high-frequency polling |
| MQTT / HTTP / Modbus TCP | Local Wi-Fi | No cloud latency and no wiring cost; short-distance, high-frequency communication where wiring is inconvenient |
How do I check the installation?
- With the inverter running and a load switched on, read the meter's real-time active power. Importing from the grid should read positive.
- Reduce the site load or increase the solar output until surplus is available. Exported power should read negative.
- If the sign is the wrong way round, turn the CT clamps round and read again.
- Confirm that the inverter lowers its output, or charges the battery, when the reading turns negative.
- Record CT size, direction, phase and the communication settings.
Check the inverter manufacturer's documentation to confirm which meter protocol and which register map it reads, and follow your local grid code for export limits.
What are the benefits?
- Helps meet grid rules that do not allow reverse power injection.
- Raises self-consumption of the solar energy generated.
- Provides accurate real-time data for reverse current control and energy management.
- Works with different inverters through standard protocols (Modbus, MQTT, HTTP).
Related OWON products
Frequently asked questions
Where do I install the CTs for anti-backflow control?
On the live conductors of the grid connection point, so that the meter measures the net power exchanged with the grid.
Which OWON meter supports RS485 Modbus RTU for an inverter?
The PC4713-W-485 has an RS485 port with Modbus RTU and Wi-Fi with HTTP, MQTT and Modbus TCP.
How fast does the inverter react?
When total active power turns negative, the inverter reduces its output within 2 seconds, or stores the surplus in the battery first.
Does it work with three-wire delta systems?
The PC4713-W-485 does not support three-phase three-wire or delta systems. It supports single-phase, split-phase and three-phase four-wire.
Related guides
- Monitoring Solar Production and Grid Usage with Clamp-On Smart Energy MetersHow bidirectional smart energy meters track grid import, export and solar production, and which OWON meters list this function on their...
- How to Choose the Right CT Clamp Size for a Smart Energy MeterLearn how to choose a CT clamp rating and inner diameter for clamp-on smart energy meters, with the OWON CT options and accuracy bands from...
- How to Install a Single-Phase DIN Rail Energy Meter and Check CT Direction: OWON PC4711Step-by-step installation of the OWON PC4711 single-phase DIN rail energy meter: DIN rail mounting, power terminal, two CT clamps, arrow...
Talk to OWON about your project
Tell us your application, target market and quantity. Our sales team replies with datasheets, protocol documents and pricing.
Send an enquiry WhatsApp +86 13159213403Or email sales@owon.com